Studies on the energy savings of vestibules and air curtains
Dialectic would like to provide retail and commercial building owners and designers a tool to help determine their need for either a vestibule or an air curtain entrance solution for their space. Building spaces vary by the type of business, but when code dictates that a vestibule is required due to its area, users need to be aware of their options.
When we meet with clients to determine their needs, they typically ask questions such as:
Vestibules and air curtains each have their positive attributes and having a designer that understands how to maximize the benefit of each will make for a better installation and user experience regardless of which option is chosen.
During the design phase of a space, the floor area comes into question as well as its impact to the design and function. Commercial building designers are required to install vestibules on the primary entrance doors leading to spaces that are equal to or greater than 3,000 square feet (ft2 ), or 298 square meters (m²), in all buildings.
Many designers are unclear on what is included in determining the 3,000 ft² floor area that defines a space. Consider this example: does an entrance door leading from a lobby attached to a corridor with a total area of 3,000 ft² meet the vestibule requirement?
When several doors leave a space greater than or equal to 3,000 ft², which doors require a vestibule?
The International Energy Conservation Code (IECC), with multiple code years adopted by different states, requires that the primary entrance doors in spaces 3,000 ft² or greater have vestibules.
This requirement typically applies to commercial spaces where the building entrance is connecting directly into the sales area or other occupancies with large lobbies, like a hotel or entertainment venue.
We will cover spaces including commercial workplaces, standalone and strip-mall retail, schools, restaurants, outpatient health care facilities, hotels and multifamily housing. We will avoid in-depth analysis of each type but will list the requirements that are applicable to each occupancy type.
The American Society of Heating, Refrigeration and Air-conditioning Engineers (ASHRAE) established a US standard that provides minimum requirements for energy efficient designs for commercial buildings with ASHRAE Standard 90.1 (Energy Standard for Buildings Except Low-Rise Residential Buildings).
New versions are updated and published every three years with the current version being ASHRAE Standard 90.1-2016. The IECC requirements are based on this standard.
|
|
This standard requires vestibules for entrance doors accessing spaces 3,000 ft2 or greater, but with some added requirements not present in the IECC. The first requirement is associated with vestibule envelope requirements.
ASHRAE requires that the exterior envelope of a conditioned vestibule comply with the requirements for a conditioned space, while the interior and exterior of an unconditioned vestibule must comply with the envelope requirements for a semi-heated space.
ASHRAE 90.1 also requires a minimum distance of 7 feet between closed interior and exterior vestibule doors. The differences between IECC and ASHRAE 90.1 are listed in the Code Citations section of this document.
Want commercial insights? Check out our blog:
A vestibule is an anteroom (antechamber) or small foyer leading into a larger space, such as a lobby, entrance hall, or passage, for purposes like waiting, withholding the larger space view and reducing heat loss. In modern architecture, a vestibule typically refers to a small room with an outer door(s) and connected with the interior of the building.
Architects and architectural designers employed by the building owner typically design vestibules. A basic vestibule design consists of an outer glass door, an inner glass door, inset floor mats, and sometimes a waiting bench.
This seems easy enough to design, but when vestibules are poorly designed issues can arise that are often related to thermal complaints (such as cold air reaching the reception desk or sales space), a lack of distance between doors, and timing between automatic outer doors closing and automatic inner doors opening. A good design requires understanding the function of the space and the habits of the customers and other users of that space.
Public entrances and high-traffic entrances are the intended doors where vestibules need to be included as part of the building design. Service doors or doors not used by the public are not the intended area for vestibules.
Consider an example building with an entry space connected to corridors with a combined total area of 3,000 ft². 2,700 ft² for the entry space and 300 ft² for the connected corridors; only those areas that cannot be closed off from the entrance door are to be included in the area total when determining if a vestibule is required.
An example of an interior vestibule |
An example of an exterior vestibule |
An air curtain is a fan-powered device that creates an invisible air barrier (sheet of air) over the doorway to separate two different environments without limiting the access of people or vehicles. This sheet of air stabilizes when it splits at a surface, such as a floor, or meets a return grille.
This stable sheet of air combined with the building’s interior air pressure resists and reduces heat transfer over an opening in the building envelope. There are two major types of air curtains: non-recirculating (most common) and recirculating.
They can be directly mounted on the wall or ceiling, exposed to view, or installed recessed into the ceiling, hidden from view (in-ceiling type). Heating, ventilation, and air conditioning (HVAC) mechanical engineers and mechanical designers typically select and design the air curtain systems employed by the building owner.
Non-recirculating air curtains are more widely used than the recirculating type because they are easier and less expensive to install and have lower maintenance costs. The height, width, and physical characteristics of the opening will indicate if the air curtain can be mounted horizontally above the door or vertically on one or both sides of the door.
A horizontal mounting above the door minimizes the chances of damaging the air curtain. Use caution when mounting a unit vertically as it is accessible to the public and can be easily damaged.
Recirculating air curtains are typically used in places with constant foot traffic such as supermarkets and store entrances. Recirculating air curtains are called air entrance systems as they are built into the entrance, usually during the original building construction.
They emit air from a discharge grille at the top of the opening and return it from the floor of the doorway. Air is returned through ductwork to the discharge grille. The non-obtrusive wide stream of low-velocity air created by recirculating air curtains is more desirable for large entrances separating two environments (indoors and outdoors).
An example of a non-recirculating air curtain © Airtècnics 2018, All rights reserved. |
|
An example of a recirculating air curtain © Airtècnics 2018, All rights reserved. |
How do you decide whether to use a vestibule or an air curtain in the entrance to your space? Here are some items to consider about using each.
Once you’ve decided on the best entrance solution for your space, the next step is to design the entrance. Here are some strategies to consider.
A vestibule is often the first and last area visitors encounter in a space, so making sure it is properly designed is key to a positive experience.
Air curtains can provide an effortless entry and exit without compromising the customer experience with mindful selection and placement.
The Americans with Disabilities Act (ADA) provides guidance on door maneuvering clearances of those that will be encountered in a vestibule design. Care should be taken in implementing these clearances for entrances with and without vestibules.
More detailed information is available through the United States Access Board (www.access-board.gov).
The provinces of Canada abide by either ASHRAE 90.1 - (Various years depending on province) or the National Energy Code of Canada for Buildings 2015/2017 (NECB).
Climate zones defined by IECC and ASHRAE are used to determine the need for vestibules and exceptions to their use such as air curtains. Climate zones 1 and 2 do not require the use of a vestibule under these codes.
All of Alaska in Zone 7 except for the following Borourghs in Zone 8.
|
US climate zones as referenced in IECC and ASHRAE 90.1
Zone 1 includes Hawaii, Guam, Puerto Rico, and the Virgin Islands |
Each state has adopted differing years of the IECC code and ASHRAE 90.1. Below is a list of those states and their current adopted code.
Some states have created their own tailored version of the IECC and are included below. Some populous municipalities have also created their own specific version of code to better address their local issues. Visit the municipality website in question for the latest updates to their code.
State-specific codes |
|
States with no mandated codes |
|
*State codes are subject to change. Municipalities may have additional or city/county specific
Only recent versions of the IECC (2018 and 2015) include the exception of using air curtains to replace vestibules. While this is a recent development in terms of the documentation, authorities having jurisdiction (AHJs) can approve of air curtains on a case by case basis if documentation and proof of an engineered solution is provided.
Given the new code exceptions many jurisdictions may be inclined to approve air curtain installation without the additional effort even if their state has not yet adopted the newer codes.
The designer must be mindful to verify all of the exceptions for a vestibule requirement in both IECC and ASHRAE 90.1 before proceeding with a vestibule or air curtain design.
The following lists the most recent codes to the oldest codes used by the states including ASHRAE 90.1-2013 as a reference. State specific codes are largely based on IECC tri-annual versions.
Building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices. Vestibules shall be designed so that in passing through the vestibule it is not necessary for the interior and exterior doors to open at the same time.
The installation of one or more revolving doors in the building entrance shall not eliminate the requirement that a vestibule be provided on any doors adjacent to revolving doors.
All building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices. Vestibules shall be designed so that in passing through the vestibule it is not necessary for the interior and exterior doors to open at the same time.
The installation of one or more revolving doors in the building entrance shall not eliminate the requirement that a vestibule be provided on any doors adjacent to revolving doors.
A door that separates conditioned space from the exterior shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices.
Vestibules shall be designed so that in passing through the vestibule it is not necessary for the interior and exterior doors to open at the same time.
Building entrances that separate conditioned space from the exterior shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices.
Vestibules shall be designed so that in passing through the vestibule it is not necessary for the interior and exterior doors to open at the same time. Interior and exterior doors shall have a minimum distance between them of not less than 7 ft when in the closed position.
The floor area of each vestibule shall not exceed the greater of 50 ft2 or 2% of the gross conditioned floor area for that level of the building. The exterior envelope of conditioned vestibules shall comply with the requirements for a conditioned space.
The interior and exterior envelope of unconditioned vestibules shall comply with the requirements for a semi-heated space.
Selecting the right entry system for your commercial space is an important decision, impacting the cost, user comfort and design aspects of your project
The following studies can give you more extensive information on the energy savings of vestibules and the use of vestibules and air curtains in specific climate zones.
These studies build upon other studies that have been performed over the years to produce the most complete picture of what using each system means for a building owner. The studies can inform the building owner about how using one system versus the other translates into a particular level of energy savings.
A Pacific Northwest National Laboratory (PNNL) paper titled “Energy Saving Impact of ASHRAE 90.1 Vestibule Requirements: Modeling of Air Infiltration through Door Openings” evaluated the energy saving potential for vestibules using whole building energy simulation tools.
This can be used by clients and owners as a guide to determining where a vestibule is required. The prototype model building table below illustrates the typically encountered entrance zone areas where a vestibule would be mandated based on the area. Architects are mindful of this and try to avoid being locked into a vestibule if that is not part of their design intent.
The exceptions to each prototype are identified with a number next to the building prototype name when it corresponds to all climate zones and a number next to yes or no confirmation when it corresponds to a particular climate zone. The exceptions are slightly different for the IECC versions of the code and should be verified before proceeding with design.
Energy Saving Impact of ASHRAE 90.1 Vestibule Requirements: Modeling of Air Infiltration through Door Openings, Table 2, page 8. Pacific Northwest National Laboratory – U.S. Department of Energy
Door traffic is a good indicator of whether a vestibule or air curtain will impact the energy savings or the user’s experience. High traffic entrances will benefit from not having a vestibule that might impede users trying to enter the space.
Ease of entry into the space is also dependent on the vesibule design. In addition, a poorly designed vestibule ceases to save energy as the doors are held open for extended periods while people make their way through the entry.
The table below illustrates both the peak and off-peak door-opening frequency for each building type. Door-opening frequency due to traffic directly translates into energy loss of a space.
*The door-opening frequency for peak hour can be estimated based on the number of occupants in a building. For retail and strip-mall stores, it is assumed that customers would use entrance door two times within 1 hour (i.e., once they enter and once they leave the store). However, for other building types it can be safely assumed that people stay longer than 1 hour in the building and use the entrance door once within 1 hour when they enter or leave. Therefore, the door-opening frequency for peak hour can be estimated to be equal to the number of occupants in all prototypical buildings except retail and strip-mall stores.
Energy Saving Impact of ASHRAE 90.1 Vestibule Requirements: Modeling of Air Infiltration through Door Openings, Table 5, page 11. Pacific Northwest National Laboratory – U.S. Department of Energy
The results for vestibule energy savings is provided below in a national weighted-average savings for each building prototype. The results provide general observations that can be used by the designer in choosing to use a vestibule even where it is not required by code.
*The weighting factors used to calculate national average savings are different for each building and each climate zone. The weighting factors, as well as the method to estimate the weighting factors and their values can be found in PNNL reports
Energy Saving Impact of ASHRAE 90.1 Vestibule Requirements: Modeling of Air Infiltration through Door Openings, Table 8, page 17. Pacific Northwest National Laboratory – U.S. Department of Energy
An Air Movement and Control Association International, Inc. (AMCA) study, “Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use,” evaluated the effectiveness of air curtains compared to vestibules and determined that air curtains had the potential to consistently meet or outperform vestibules in terms of energy savings.
The study took other real-world factors into consideration to determine air curtain performance that included the building entrance orientation, frequency of use, the balance of the building HVAC system (pressure) affecting air infiltration/exfiltration, and the overall energy performance of the air curtain.
These additional factors were shown to be as important as door-opening frequency. Based on the results of the modeled building and the air curtain in this study, considering its lower initial cost and space saving benefit, an air curtain should be a good alternative to the vestibule for the climate zones of 3-8.
The modeled air curtain door reduced energy consumption by 0.3% to 2.2% in the study. The results from this study are based on a specific building type, specific parameters, and a specific modeling method of the air curtains.
While this shows a good result for air curtains, generalization of the conclusions may need further analysis based on the changes to the modeling scenario. This includes expanding the opening to multiple doors rather than a single door and varying the real-world factors for the case actually being considered by the building owner and/or designer.
Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use, Table 6, page 9. © Copyright 2015 Air Movement and Control Association International, Inc.
The PNNL study and the AMCA study are to be taken at face value as they are models rather than real-world testing results, but they are a good indicator of what would be encountered by using either a vestibule or an air curtain.
They inform a building owner of what to expect from either system so that a designer (architect or HVAC mechanical) can make adjustments to improve the final design and benefit the end user. There are real-world test results from air curtain manufacturers, but those results vary from each manufacturer and the models tested.
While some may argue that a vestibule is better than an air curtain or vice versa, much of the decision to install one over the other comes down to installed cost, the function of the space, the traffic level and overall experience the owner wants the occupants to have when entering the space.
The overall effectiveness of an air curtain or vestibule is dependent on the design and application. The designer has the responsibility of informing both the architect and the building owner about what each option is capable of and the many factors that come into play in making a choice.
Misapplication of either entrance system can work against what the building owner is trying to accomplish for the space. The designer must be aware of all local code requirements and experienced enough to properly design the system.
Air curtain designs and performance vary from manufacturer to manufacturer, so research by the designer is necessary for an effective installation. Vestibule designs can be even more varied and need input from multiple disciplines for an effective design.
Informing building owners about the requirements and choices available can have lasting benefits for both the owners and the building users.
We have the experience in your climate area, knowledge of local codes and design expertise to help you decide on and design your ideal entrance solution. We can work with you and your project partners and provide sustainable solutions for your industry.
REFERENCES
2009 and 2012 IECC; ASHRAE 90.1-2007 and 2010, Vestibule Requirements in Commercial Buildings. U.S. Department of Energy.
|